Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Standards
IEC
Current Type
AC
Rated Voltage (U<sub>r</sub>)
690 V
Rated Operational Voltage
690 V AC
Rated Current (I<sub>n</sub>)
4000 A
Rated Short-time Withstand Current Low Voltage (I<sub>cw</sub>)
for 1 s 40 kA
Number of Poles
4P
Version
W
Configuration Type
Mounted only
Product Type
Direct Replacement Legrand DMX, DPX to Emax 2 IEC
Sub-type
E4.2
Operational Derating
Derating to 3600A in case of cassettes with vertical (VR) terminals. Derating to 3450A in case of cassettes with horizontal (HR) or front (F) terminals
Product Net Width
538 mm
Product Net Height
374 mm
Product Net Depth / Length
376 mm
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)