Short Description: ABB's XT2L 160 TMD 16/300 3P is a fixed three-pole moulded case circuit breaker with front terminals and thermomagnetic release, suitable for AC/DC applications up to 690V and 16-300A.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
L
Product Highlights
1. Reliable Performance
The XT2L 160 TMD 16/300 3P ensures reliable operation with a high short-circuit breaking capacity, making it ideal for demanding electrical systems.
2. Thermomagnetic Release
Equipped with a thermomagnetic release mechanism, this circuit breaker provides both thermal and magnetic protection, ensuring safe and efficient operation.
3. Versatile Application
Designed for AC/DC applications, this circuit breaker supports a wide range of voltages and currents, making it suitable for various industrial and commercial settings.
4. High Durability
Built to withstand heavy usage, the XT2L 160 TMD 16/300 3P offers excellent electrical and mechanical durability, ensuring long-term reliability in harsh environments.
5. Compliance and Certifications
Meets IEC standards and is certified by LR, GL, and CE, ensuring compliance with international safety regulations and standards.
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH102225R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?