ABB XT2H 160 TMA 160/1600: A high-performance, four-pole circuit breaker with thermomagnetic release for AC/DC applications, ensuring reliable power distribution and exceptional short-circuit breaking capacity.
Specifications for XT2H160 TMA160/1600 PMP 4P N=100%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
P
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 19.0 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
H
Product Highlights
Product Feature
1. High Short-Circuit Breaking Capacity The ABB XT2H 160 TMA 160/1600 features a rated service short-circuit breaking capacity of up to 100 kA at 220-240 V AC, 70 kA at 380-415 V AC, and 65 kA at 440 V AC, ensuring reliable operation under demanding conditions.
Product Feature
2. Thermomagnetic Release Equipped with a thermomagnetic release, this circuit breaker provides a robust and reliable mechanism for interrupting short circuits, ensuring the safety and integrity of electrical systems.
Product Feature
3. Wide Operating Range Designed to operate in both AC and DC environments, the XT2H 160 TMA 160/1600 is versatile and can handle a wide range of electrical currents, from 800 to 1600 A.
Product Feature
4. Durable Construction Built to withstand the rigors of electrical systems, this circuit breaker has a mechanical durability of up to 25,000 cycles at 240 cycles per hour, ensuring long-lasting performance.
Product Feature
5. Compliance with International Standards The ABB XT2H 160 TMA 160/1600 meets IEC standards for short-circuit performance, ensuring that it operates safely and efficiently in a variety of electrical environments.
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Plug-In Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100707R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?