High-performance, fixed three-pole circuit breaker with front terminals and thermomagnetic release, designed for robust power distribution in industrial settings.
Product ModelXT2V 160 TMD16/300 F F 3P
Material Number2TFC000617R1001
Product ID93506
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Robust Electrical DurabilityThe XT2V 160 TMD 16-300 3P FF is designed to withstand 240 cycles per hour and 25,000 cycles in total, ensuring reliable operation under heavy electrical loads.
2
2. Mechanical DurabilityWith a mechanical durability of 25,000 operations, this circuit breaker is built to last, providing consistent performance over extended periods.
3
3. Thermomagnetic ReleaseEquipped with a thermomagnetic release (TMD), the XT2V 160 TMD 16-300 3P FF ensures safe and efficient operation by automatically tripping in case of overheating or short circuits.
4
4. High Short-Circuit Breaking CapacityThe circuit breaker has a rated service short-circuit breaking capacity of 200 kA at 220 V AC and 150 kA at 380 V AC, making it suitable for high-power applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
1SDL000190R0001
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Product Name
Moulded Case Circuit Breaker
5
5. Compliance with International StandardsThe XT2V 160 TMD 16-300 3P FF complies with IEC standards, ensuring it meets the highest safety and performance requirements for industrial power distribution systems.
Product Type
CB
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.30 W
Rated Current (In)
16 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
V
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)