The ABB XT2L 160 TMA 50-500 3P FF is a fixed three-pole circuit breaker with front terminals and thermomagnetic release, suitable for AC/DC applications. It offers high electrical durability and mechanical reliability, making it ideal for power distribution in various installations.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Product Highlights
1. High Electrical Durability
The XT2L 160 TMA 50-500 3P FF can withstand up to 25,000 electrical operations, ensuring long-lasting performance in demanding environments.
2. Thermomagnetic Release
Equipped with a thermomagnetic release, this circuit breaker provides reliable and efficient operation, automatically tripping in case of an overload or short circuit.
3. Front Terminal Connection
The front terminal connection makes installation and maintenance easier, reducing downtime and increasing overall efficiency.
4. Wide Operating Range
Designed to operate at currents ranging from 250 to 500 A, this circuit breaker is versatile and can be used in various electrical applications.
5. Compliance with International Standards
The XT2L 160 TMA 50-500 3P FF meets IEC standards and is CE certified, ensuring compliance with international safety and performance regulations.
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFC000598R1001