The ABB XT2L 160 TMD 32/320 3P F F is a fixed three-pole moulded case circuit breaker with front terminals and thermomagnetic release. It offers high reliability and efficiency for power distribution applications.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Product Highlights
1. High Reliability and Efficiency
The XT2L 160 TMD 32/320 3P F F is designed to provide reliable and efficient power distribution, ensuring minimal downtime and maximum performance.
2. Thermomagnetic Release
Equipped with a thermomagnetic release, this circuit breaker automatically trips in case of an overload or short circuit, ensuring safety and preventing damage to the electrical system.
3. Front Terminal Connection
The front terminal connection makes installation and maintenance easier, reducing the time and effort required for setup and repair.
4. Compliance with IEC Standards
The XT2L 160 TMD 32/320 3P F F meets IEC standards, ensuring compliance with international safety and performance regulations.
5. Wide Range of Applications
Suitable for a variety of applications including transformer, generator, and installation protection, this circuit breaker is versatile and reliable in different electrical settings.
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFC000596R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.