Short Description: The ABB XT1N 160 TMD 63/630 4P+RC Inst is a fixed, four-pole circuit breaker with front terminals and a thermomagnetic release (TMD). It is designed for 63 A and 690 V applications, ensuring reliable and efficient operation in various electrical systems.
Specifications for XT1N160 TMD63/630 FFC 4P+RC Inst
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
2.7 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 4.3 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Product Highlights
1. Reliable Operation
The ABB XT1N 160 TMD 63/630 4P+RC Inst is engineered to provide consistent and reliable operation, ensuring the safety of your electrical system.
2. High Performance
With a thermomagnetic release (TMD), this circuit breaker offers high performance in interrupting short circuits, making it ideal for demanding applications.
3. Efficient Design
The front terminal connection type simplifies installation and reduces maintenance time, enhancing overall efficiency in your electrical setup.
4. Compliance with IEC Standards
The product meets IEC standards, ensuring that it adheres to the highest safety and performance requirements, providing peace of mind for your electrical projects.
5. Versatile Application
Designed for 63 A and 690 V applications, this circuit breaker is versatile and can be used in a variety of electrical systems, including transformers, generators, and installations.
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100494R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?