The ABB XT1S 160 TMD 125-1250 3P FF is a fixed, three-pole circuit breaker with front terminals and thermomagnetic release, suitable for AC/DC applications. It provides reliable protection and high performance in power distribution systems.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 63.75 kA (230 V AC) 63.75 kA (240 V AC) 63.75 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
S
Standards
IEC60947-2 GB/T 14028.2
Product Highlights
1. Reliable Protection
The XT1S 160 TMD 125-1250 3P FF offers reliable protection in power distribution systems, ensuring the safety of your electrical infrastructure.
2. High Performance
Designed for high-performance applications, this circuit breaker provides excellent electrical and mechanical durability, ensuring it can withstand demanding conditions.
3. Versatile Compatibility
Compatible with both AC and DC currents, this circuit breaker is versatile and can be used in a variety of electrical systems.
4. Efficient Operation
With a rated current of 160 A and a short-circuit breaking capacity of up to 50 kA, this circuit breaker ensures efficient operation and effective short-circuit protection.
5. Easy Installation
The front terminal connection and simplified installation process make it easy to integrate into your existing electrical setup, reducing downtime and increasing productivity.
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100127R1001