Short Description: ABB's XT1N 160 TMD 160-1600 4P FF N=100% is a robust, four-pole moulded case circuit breaker with thermomagnetic release, designed for transformer, generator, and installation protection, ensuring reliable short-circuit breaking capacity and IEC compliance.
Specifications for XT1N160 TMD160/1600 FFC 4P N=100%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC/DC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Product Highlights
1. High Short-Circuit Breaking Capacity
The XT1N 160 TMD 160-1600 4P FF N=100% boasts impressive short-circuit breaking capacities, including 50 kA at 220-240 V AC, 36 kA at 380-440 V AC, and 15 kA at 500 V AC.
2. Thermomagnetic Release
Equipped with a thermomagnetic release (TMD), this circuit breaker ensures reliable operation under various conditions, providing a safe and efficient shutdown in case of an overload or short circuit.
3. IEC Compliance
Designed to meet IEC standards, the XT1N 160 TMD 160-1600 4P FF N=100% guarantees compliance with international safety and performance requirements, ensuring it can be used in a wide range of applications.
4. Four-Pole Configuration
The four-pole configuration allows for flexible installation in various electrical systems, making it suitable for both new installations and upgrades in existing infrastructure.
5. Reliable Performance
With a high operational voltage rating of 690 V AC and a rated current of 160 A, this circuit breaker offers reliable performance in demanding electrical environments, including transformer and generator applications.
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100110R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.