ABB's XT4N 160 Ekip LSIG R63 FF 3P circuit breaker provides robust AC protection with a rated current of 63A, ensuring reliable operation in high-performance electrical systems.
Product ModelXT4N 160 Dip Mea. LSIG R63 F F 3P
Material Number2TFC000822R1001
Product ID91565
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable AC ProtectionThe XT4N 160 Ekip LSIG R63 FF 3P circuit breaker offers dependable AC protection, ensuring the safety and efficiency of your electrical system.
2
2. High-Performance CapabilityDesigned for high-performance applications, this circuit breaker can handle demanding electrical loads with ease, providing consistent performance under various conditions.
3
3. Solid-State Release MechanismEquipped with a solid-state release mechanism, the XT4N 160 Ekip LSIG R63 FF 3P ensures fast and reliable tripping in case of short circuits, minimizing downtime and risk.
4
4. Compliance with IEC StandardsMeets IEC standards for safety and performance, ensuring compliance with international electrical safety regulations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
1SDL000190R0001
Product Net Width
105 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.5 kg
Product Name
Moulded Case Circuit Breaker
5
5. Versatile ApplicationSuitable for a wide range of applications, including transformer and generator installations, this circuit breaker offers flexibility and reliability in various electrical configurations.
Product Type
CB
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.40 W
Rated Current (In)
63 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip Measuring LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)