The ABB XT1B 160 TMD 63/630 4P FFC is a fixed four-pole moulded case circuit breaker with front terminals and thermomagnetic release, ideal for power distribution applications. It offers high electrical and mechanical durability, ensuring reliable operation in a variety of settings.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.5 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA
(220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Short-Circuit Performance Level
B
Standards
IEC60947-2 GB/T 14028.2
Product Highlights
1. Reliable Operation
The ABB XT1B 160 TMD 63/630 4P FFC is designed with a thermomagnetic release mechanism, providing reliable operation and quick response to short circuits.
2. High Durability
With an electrical durability of 120 cycles per hour and a mechanical durability of up to 25,000 cycles, this circuit breaker ensures long-lasting performance in demanding environments.
3. Versatile Application
Suitable for AC/DC currents, this circuit breaker can be used in a wide range of applications, including power distribution in industrial settings and commercial facilities.
4. Efficient Design
The fixed four-pole design with front terminals allows for easy installation and maintenance, reducing downtime and increasing overall efficiency.
5. Compliance with Standards
The XT1B 160 TMD 63/630 4P FFC meets IEC standards, ensuring compliance with international safety and performance regulations, providing peace of mind for users.
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100027R1001