The ABB XT1B 160 TMD 40-450 3P F F is a high-performance, three-pole moulded case circuit breaker with front terminals and a thermomagnetic release. It offers excellent electrical durability and short-circuit breaking capacity, making it suitable for various power distribution applications.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 11.5 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA
(220 V AC) 25 kA (230 V AC) 25 kA (240 V AC) 25 kA (380 V AC) 18 kA (415 V AC) 18 kA (440 V AC) 15 kA (500 V AC) 8 kA (525 V AC) 6 kA (690 V AC) 3 kA (250 V DC) 2 Poles in Series 18 kA (500 V DC) 3 Poles in Series 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
B
Product Highlights
1. High Short-Circuit Breaking Capacity
The XT1B 160 TMD 40-450 3P F F boasts a high short-circuit breaking capacity of up to 25 kA at various voltage levels, ensuring reliable operation under demanding conditions.
2. Thermomagnetic Release
Equipped with a thermomagnetic release (TMD), this circuit breaker provides precise and reliable operation, automatically tripping in case of excessive current.
3. Front Terminal Connection
The front terminal connection makes installation and maintenance easier, reducing the need for complex wiring configurations.
4. Electrical Durability
Designed to withstand 120 cycles per hour with a total of 8,000 cycles, this circuit breaker ensures long-lasting performance in harsh electrical environments.
5. Compliance with International Standards
Meets IEC standards, ensuring compliance with international safety and performance requirements, making it a trusted choice for global applications.
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100005R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.