Short Description: ABB XT4N 160 Dip MEA LSIG R100 FF 4P - 4-pole circuit breaker with high reliability, precise metering, and robust short-circuit breaking capacity.
Product ModelXT4N 160 Dip Mea. LSIG R100 F F 4P
Material Number2TFC000833R1001
Product ID90397
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. High ReliabilityThe ABB XT4N 160 Dip MEA LSIG R100 FF 4P is designed to provide consistent performance in demanding electrical applications, ensuring your system operates reliably.
2
2. Precise MeteringEquipped with advanced metering capabilities, this circuit breaker offers precise measurements, helping you manage your electrical distribution efficiently.
3
3. Robust Short-Circuit Breaking CapacityWith a rated ultimate short-circuit breaking capacity (Icu) of up to 70 kA, this circuit breaker can handle high short-circuit currents, protecting your equipment from damage.
4
4. Versatile Installation OptionsAvailable in fixed, plug-in, and withdrawable configurations, the ABB XT4N 160 Dip MEA LSIG R100 FF 4P can be easily integrated into various electrical systems, including those requiring DIN rail mounting.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
1SDL000190R0001
Product Net Width
140 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
3.5 kg
Product Name
Moulded Case Circuit Breaker
5
5. Compliance with International StandardsDesigned to meet IEC 60947-2 standards, this circuit breaker ensures compliance with international safety and performance requirements, providing peace of mind in your electrical installations.
Product Type
CB
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 3.50 W
Rated Current (In)
100 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip Dip Measuring LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT4
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)