The ABB XT2L160 LS/I R100 WMP 3P circuit breaker is a high-performance, three-phase device designed for reliable power distribution. With a rated current of 160 A and a short-circuit breaking capacity of 150 kA, it provides robust protection against electrical faults.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA
Rated Uninterrupted Current (Iu)
160 A
Release
Ekip LS/I
Product Highlights
1. Reliable Power Protection
The ABB XT2L160 LS/I R100 WMP 3P circuit breaker is engineered to provide reliable power protection, ensuring the safe operation of your electrical system.
2. High Current Rating
With a rated current of 160 A, this circuit breaker is suitable for a wide range of applications, including industrial and commercial settings.
3. Efficient Short-Circuit Protection
Featuring a short-circuit breaking capacity of 150 kA, it efficiently handles short-circuit events, minimizing damage to your electrical equipment.
4. Versatile Installation
Designed for 3-phase applications, this circuit breaker offers flexibility in installation, making it a versatile choice for various electrical configurations.
5. Compliance with International Standards
The ABB XT2L160 LS/I R100 WMP 3P circuit breaker complies with international standards such as IEC60947-1 and EN60947-1, ensuring high-quality performance and safety.
Release Type
EL
Remarks
ATLAS
Short-Circuit Performance Level
L
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Withdrawable Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH102139R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.