Short Description: The ABB XT1N 160 TMD 32/450 4P+RC Inst is a four-pole molded case circuit breaker with a thermomagnetic release, ideal for power distribution in AC/DC systems. It offers high reliability and efficiency, ensuring safe and uninterrupted operation.
Specifications for XT1N160 TMD32/450 FFC 4P+RC Inst
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
2.7 kg
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
Current Type
AC
Electrical Durability
8000 cycle 120 cycles per hour
Mechanical Durability
25000 cycle 240 cycles per hour
Number of Poles
4P
Power Loss
at Rated Operating Conditions per Pole 2.1 W
Rated Current (In)
32 A
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMD
Product Highlights
1. High Reliability and Efficiency
The ABB XT1N 160 TMD 32/450 4P+RC Inst is designed to provide reliable and efficient power distribution, ensuring minimal downtime and maximum system performance.
2. Thermomagnetic Release
Equipped with a thermomagnetic release (TMD), this circuit breaker ensures safe and controlled operation in various electrical conditions, including short circuits and overloads.
3. AC/DC Compatibility
Suitable for both AC and DC applications, this circuit breaker can handle a wide range of electrical systems, making it versatile and adaptable to different environments.
4. High Short-Circuit Breaking Capacity
With a high short-circuit breaking capacity, the XT1N 160 TMD 32/450 4P+RC Inst can handle significant electrical surges, protecting your equipment and ensuring continuous operation.
5. Compliance with IEC Standards
Designed and manufactured to meet IEC standards, this circuit breaker ensures compliance with international safety and performance regulations, providing peace of mind for users.
Release Type
TM
Remarks
ATLAS
Short-Circuit Performance Level
N
Standards
IEC60947-2 GB/T 14028.2
Sub-type
XT1
Terminal Connection Type
Front for Copper Cables
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFH100491R1001