The ABB XT2L 160 TMA 80/800 FF 4P is a fixed four-pole moulded case circuit breaker with front terminals and thermomagnetic release. It supports a rated current of 80 A and is designed to handle short-circuit currents up to 800 A, making it ideal for various industrial and commercial applications.
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Release
TMA
Product Highlights
1. Reliable Performance
The ABB XT2L 160 TMA 80/800 FF 4P is engineered to provide consistent and reliable performance, ensuring uninterrupted power supply in critical applications.
2. High Current Handling
With a rated current of 80 A and a short-circuit current handling capability of up to 800 A, this circuit breaker is designed to handle demanding electrical loads.
3. Thermomagnetic Release
The thermomagnetic release mechanism ensures safe and efficient operation by automatically tripping the circuit in case of overheating or short circuits.
4. Front Terminal Connection
The front terminal connection type simplifies installation and maintenance, reducing downtime and increasing overall efficiency.
5. Compliance with IEC Standards
The XT2L 160 TMA 80/800 FF 4P complies with IEC standards, ensuring it meets the highest safety and performance criteria for electrical equipment.
Release Type
TM
Short-Circuit Performance Level
L
Standards
IEC 60947-2 GB/T 14028.2
Sub-type
XT2
Terminal Connection Type
Fixed Circuit-Breakers
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
2TFC000611R1001
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.