The ABB XT2N 125 Ekip DIP LSIG In=10A 3P FF UL/CSA is a high-performance moulded case circuit breaker designed for reliable and efficient electrical protection. It features electronic trip units, adjustable protection settings, and compliance with UL and CSA standards.
Specifications for XT2N 125 Ekip Dip LSIG In=10A 3p F F UL/CSA
Parameter
Value
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
UL
Sub-type
XT2
Interrupting Rating acc. to UL489
Product Highlights
1. Reliable Protection
The ABB XT2N 125 Ekip DIP LSIG In=10A 3P FF UL/CSA offers reliable protection against overloads, short circuits, and earth faults. Its electronic trip units ensure swift and accurate detection of electrical anomalies.
2. Adjustable Protection Settings
This circuit breaker allows for adjustable protection settings, enabling you to customize the protection levels according to your specific needs. The settings range from 0.4 to 1 times the rated current for overload protection and 1 to 10 times the rated current for short-circuit protection.
3. Compliance with Standards
The XT2N 125 Ekip DIP LSIG In=10A 3P FF UL/CSA is compliant with UL 489 and CSA C22.2 standards, ensuring it meets the highest safety and performance requirements.
4. High Durability
Designed for continuous operation, this circuit breaker can withstand up to 25,000 operations at no load, making it a durable choice for demanding electrical applications.
5. Versatile Connectivity Options
The XT2N 125 Ekip DIP LSIG In=10A 3P FF UL/CSA offers ring-lug or bar connections, providing flexibility in terms of installation and maintenance. This ensures easy integration into various electrical systems.
(240 V AC) 65 A (480 V AC) 25 A (600 V AC) 18 A
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA102042R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.