The ABB XT2N 125 Ekip DIP LSIG is a 125A, 3-pole moulded case circuit breaker designed for continuous operation with electronic trip units. It provides comprehensive protection against overload, short-circuit, and earth faults, ensuring reliable electrical safety.
Specifications for XT2N 125 Ekip Dip LSIG In=60A 3p F F UL/CSA
Parameter
Value
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.2 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Power Loss
at Rated Operating Conditions per Pole 1.50 W
Rated Current (In)
60 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V AC
Release
Ekip Dip LSIG
Release Type
EL
Short-Circuit Performance Level
N
Standards
UL
Sub-type
XT2
Interrupting Rating acc. to UL489
Product Highlights
1. Advanced Protection Features
The XT2N 125 Ekip DIP LSIG offers robust protection against overload, short-circuit, and earth faults, ensuring the safety and reliability of your electrical system.
2. High Performance
Designed for continuous operation at 100% of rating, this circuit breaker is suitable for both thermal magnetic and electronic trip units, providing reliable performance in various applications.
3. Compliance with Standards
Compliant with UL 489 and CSA C22.2 standards, this product meets the highest safety and performance requirements, ensuring it is suitable for a wide range of electrical installations.
4. Versatile Connectivity Options
Available with ring-lug or bar connections, the XT2N 125 Ekip DIP LSIG offers flexibility in installation, making it easy to integrate into various electrical systems.
5. Mechanical Durability
With a mechanical durability of 25,000 operations at no load, this circuit breaker is built to withstand the demands of frequent use, ensuring long-lasting performance and reliability.
(240 V AC) 65 A (480 V AC) 25 A (600 V AC) 18 A
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
Manufacturer ID
1SDA102044R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.