ABB NF40E-13: A versatile contactor relay for 100-250V AC/DC, supporting 50/60Hz frequencies. Ideal for industrial control circuits with a wide voltage range.
Product ModelNF40E-13
Material Number1SBH137001R1340
Product ID87116
Stock on Request
Last updated: 8/29/2026
Key Features
1
Feature1. Versatile Voltage Compatibility The ABB NF40E-13 supports control voltages between 24 to 500V AC/DC, making it adaptable to a wide range of industrial applications.
2
Feature2. High Performance and Reliability Designed with robust components, this contactor relay ensures reliable operation in diverse environments, including varying temperatures and altitudes.
3
Feature3. Wide Frequency Compatibility Compatible with both 50Hz and 60Hz frequencies, the NF40E-13 is suitable for use in different regions and applications.
4
Feature4. Electronic Coil Interface Equipped with an electronic coil interface, the NF40E-13 offers efficient and precise control over the switching of auxiliary and control circuits.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
45 mm
Product Net Depth / Length
77 mm
Product Net Height
86 mm
Product Net Weight
0.27 kg
Number of Auxiliary Contacts NO
4
Number of Auxiliary Contacts NC
0
5
Feature5. Compliance with International Standards Meets international standards such as IEC 60947-5-1, UL 508, and CSA C22.2 N°14, ensuring safety and reliability in various industrial settings.
Standards
IEC/EN 60947-1, IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14-13
(500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)
for 0.1 s 140 A for 1 s 100 A
Maximum Electrical Switching Frequency
(AC-15) 1200 cycles per hour (DC-13) 900 cycles per hour
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 1 A / 72 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.27 A / 60 W (250 V) 0.27 A / 68 W (400 V) 0.15 A / 60 W (500 V) 0.13 A / 65 W (600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)
acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Mechanical Switching Frequency
6000 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms Between Coil De-energization and NO Contact Opening 11 ... 95 ms Between Coil Energization and NC Contact Opening 38 ... 90 ms Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Auxiliary Circuit 11 in·lb Control Circuit 11 in·lb
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Closed, Shock Direction: B1 25 g Open, Shock Direction: B1 5 g Shock Direction: A 30 g Shock Direction: B2 15 g Shock Direction: C1 25 g Shock Direction: C2 25 g
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz
Object Classification Code
K
ETIM 7
EC000196 - Contactor relay
ETIM 8
EC000196 - Contactor relay
ETIM 9
EC000196 - Contactor relay
eClass
V11.0 : 27371001
UNSPSC
39121529
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching
E-Number (Finland)
3706415
E-Number (Sweden)
3211456
Manufacturer ID
1SBH137001R1340