4-pole load break switch-disconnector with front-operated, base-mounted design, black IP65 handle, and terminal bolt kit. Ideal for high current applications.
Product ModelOT160EV22P
Material Number1SCA120537R1001
Product ID86669
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable PerformanceThe ABB OT160EV22P is designed to provide reliable performance in high current applications, ensuring consistent operation under various conditions.
2
2. Robust ConstructionBuilt with a robust base-mounted design, this switch-disconnector offers durability and long-lasting service, making it suitable for demanding electrical environments.
3
3. Easy OperationFeaturing a front-operated mechanism, the OT160EV22P allows for easy and accessible operation, reducing the risk of accidents and improving overall safety.
4
4. High Current CapacityWith a conventional thermal current (Ithe) of 160 A, this switch-disconnector is capable of handling high current loads, making it ideal for various industrial and commercial applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Degree of Protection
Front IP00
Environmental Information
1SCC301265D0201
Pollution Degree
3
Product Net Width
185.5 mm
Product Net Height
150 mm
Product Net Depth / Length
82.5 mm
5
5. Compliance and SafetyThe OT160EV22P is ROHS compliant and features a black IP65 handle and shaft, ensuring it meets stringent safety and environmental standards. The inclusion of a terminal bolt kit further enhances its usability and reliability.
6
6. Versatile Mounting OptionsThe switch-disconnector offers flexibility in mounting options, allowing it to be easily integrated into different electrical systems, including base mounting and DIN-rail mountability for 40A applications.
7
7. High Voltage ToleranceWith a rated impulse withstand voltage (Uimp) of 12 kV, the OT160EV22P is designed to handle high voltage conditions, providing added protection against electrical surges and faults.
Product Net Weight
1.7 kg
Conventional Free-air Thermal Current (Ith)
Π= 40 °C 200 A
Conventional Thermal Current (Ithe)
Fully Enclosed 160 A
Degree of Protection
Front IP00
Distance Between Phases
Standard
Fourth Pole Position
Right Side
Fourth Pole Type
Switched - Simultaneous Function
Handle Color
Black
Handle Type
Handle and shaft included
Lock Type
Yes
Mechanical Durability
20000
Mounting Type
Base mounting
Number of Poles
4P
Operating Mode
Front operated
Pollution Degree
3
Position of Line Terminals
Top In - Bottom Out Bottom In - Top Out
Power Loss
at Rated Operating Conditions per Pole 3.2 W
Rated Conditional Short-Circuit Current (Inc)
(315 A fuse, 500 V) 100 kA (355 A fuse, 690 V) 80 kA (250 A fuse, 690 V) 100 kA