The ABB XT2H 125 Ekip LS/I 10A 4P FF UL/CSA is a high-performance, four-pole circuit breaker with solid-state release and front terminals. It meets UL/CSA standards, ensuring reliable and efficient power distribution while adhering to eco-friendly design principles.
Specifications for XT2H 125 Ekip LSI In=10A 4p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.6 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.10 W
Rated Current (In)
10 A
Rated Frequency (f)
50/60 Hz
Rated Insulation Voltage (Ui)
1000 V AC
Rated Operational Voltage
690 V AC
Rated Uninterrupted Current (Iu)
160 A
Product Highlights
1. High Performance and Reliability
The ABB XT2H 125 Ekip LS/I 10A 4P FF UL/CSA circuit breaker is designed to provide reliable performance in a variety of applications, ensuring consistent operation under various load conditions.
2. Eco-Friendly Design
This product adheres to ABB's eco-friendly design principles, including a recyclability rate of 58.1% and compliance with the EN45555 standard for circular design. It is part of ABB's commitment to reducing waste and promoting sustainability.
3. Solid-State Release
Equipped with a solid-state release mechanism, this circuit breaker offers fast and efficient operation. The EL release type ensures quick and reliable tripping in case of an overload or short circuit.
4. Front Terminal Connection
The front terminal connection type allows for easy installation and maintenance. The bolt terminal type with a tightening torque of 6 N·m ensures secure connections without the need for lugs.
5. Compliance with UL/CSA Standards
The ABB XT2H 125 Ekip LS/I 10A 4P FF UL/CSA meets the stringent standards set by UL and CSA, ensuring that it is safe and reliable for use in a wide range of applications. It is certified for intrinsic safety and has no additional certification needed beyond its inherent safety features.
Rated Voltage (Ur)
690 V AC
Recommended Screw Driver
Main Circuit M6
Release
Ekip LSI
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 A (480 V AC) 65 A (600 V AC) 25 A
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4934 >> 4 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074975R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.