ABB's XT2V 160 TMD 1.6-16 3p FF is a fixed three-pole circuit breaker with front terminals and thermomagnetic release, designed for reliable system protection in AC/DC applications.
Product ModelXT2V 160 TMD 1,6-16 3p F F
Material Number1SDA067672R1
Product ID86489
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Robust Electrical DurabilityThe XT2V 160 TMD 1.6-16 3p FF is engineered to withstand 240 cycles per hour and 25,000 cycles in total, ensuring long-lasting performance in demanding electrical environments.
2
2. Compliance with IEC StandardsThis circuit breaker meets the stringent requirements of IEC standards, ensuring it is suitable for a wide range of applications, including power distribution and generator protection.
3
3. Thermomagnetic ReleaseEquipped with a thermomagnetic release (TMD), the XT2V 160 TMD 1.6-16 3p FF provides reliable and efficient short-circuit protection, ensuring the safety of your electrical system.
4
4. Versatile ApplicationDesigned for both AC and DC applications, this circuit breaker is versatile and can be used in various settings, including communication systems and industrial power distribution.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Power Distribution
5
5. Compact DesignWith dimensions of 90 mm x 130 mm x 82.5 mm and a weight of 1.1 kg, the XT2V 160 TMD 1.6-16 3p FF is compact and easy to integrate into your existing electrical infrastructure.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2 W
Rated Current (In)
1.6 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
16 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
1.12...1.6 A
Short-Circuit Performance Level
V
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)