Short Description: ABB XT3N 250 TMG 100-400 4P FF - High-performance, four-pole circuit breaker with thermomagnetic release and front terminals for reliable generator protection.
Product ModelXT3N 250 TMG 100-400 4p F F
Material Number1SDA068260R1
Product ID86462
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable ProtectionThe XT3N 250 TMG 100-400 4P FF offers robust protection against short circuits, ensuring the safety and reliability of your electrical system.
2
2. Efficient OperationWith a thermomagnetic release mechanism, this circuit breaker provides fast and efficient operation, minimizing downtime and maximizing system performance.
3
3. Versatile ApplicationDesigned for generator protection, this four-pole circuit breaker can be used in a variety of applications, including transformer and installation protection.
4
4. High DurabilityBuilt to withstand heavy usage, the XT3N 250 TMG 100-400 4P FF has a mechanical durability of up to 25,000 cycles, ensuring long-lasting performance.
5
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
140 mm
Product Net Height
150 mm
Product Net Depth / Length
70 mm
Product Net Weight
2.1 kg
Circuit Breaker Type to be Associated
Generator Protection
5. Compliance and CertificationsMeets IEC standards and is CE compliant, ensuring that the product adheres to international safety and performance regulations.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0483
Connecting Capacity Main Circuit
Busbar 85..192 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 5.6 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
400 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 27 kA (415 V AC) 36 kA (440 V AC) 19 kA (500 V AC) 15 kA (525 V AC) 9.75 kA (690 V AC) 3.75 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 20 kA (525 V AC) 13 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M8
Release
TMG
Release Type
TM
Setting Range
70...100 A
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT3
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)