The ABB XT2L 160 TMD 12,5-125 3p F F is a fixed three-pole circuit breaker with front terminals and thermomagnetic release, suitable for a wide range of applications including power distribution and generator protection. It features a high breaking capacity and is designed to meet international standards for safety and performance.
Rated Instantaneous Short-Circuit Current Setting (Ii)
125 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
Product Highlights
1. High Breaking Capacity
The XT2L 160 TMD 12,5-125 3p F F boasts a high breaking capacity, ensuring reliable operation under various short-circuit conditions. It can handle up to 160 A and 100 kA at 440 V AC, making it suitable for demanding applications.
2. Thermomagnetic Release
Equipped with a thermomagnetic release (TMD), this circuit breaker provides both thermal and magnetic protection, ensuring reliable operation in diverse environmental conditions.
3. Compliance with International Standards
The XT2L 160 TMD 12,5-125 3p F F meets international standards for safety and performance, including IEC and UL certifications, ensuring it is compatible with a wide range of electrical systems.
4. Energy Efficiency
Designed with energy efficiency in mind, this circuit breaker features high selectivity values and compact motor protection solutions, allowing for optimal sizing of circuits and equipment on the load side.
5. Sustainability
ABB’s commitment to sustainability is evident in the XT2L 160 TMD 12,5-125 3p F F, which adheres to the design for closing resource loops standard (EN45555) with a recyclability rate of 58.1%, aligning with ABB’s EcoSolutions initiative.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
8.75...12.5 A
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067637R1