The ABB XT1S 160 TMD 160-1600 4-pole circuit breaker features front terminals, thermal-magnetic release, and high short-circuit breaking capacities, making it ideal for demanding power distribution applications.
Specifications for XT1S 160 TMD 160-1600 4p F F InN=100%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1600 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
Product Highlights
1. Advanced Thermal-Magnetic Release
The XT1S 160 TMD 160-1600 features a robust thermal-magnetic release mechanism, ensuring reliable operation under various load conditions.
2. High Short-Circuit Breaking Capacity
With a high short-circuit breaking capacity of up to 85 kA at 220-240 V AC, this circuit breaker provides exceptional protection against electrical surges.
3. Front Terminal Connections
The front terminal design simplifies installation and maintenance, reducing downtime and increasing overall efficiency.
4. Wide Operating Range
Designed to operate at 50/60 Hz, this circuit breaker is versatile and can handle a wide range of applications, from industrial to commercial settings.
5. High Reliability and Durability
Built with high-quality materials and designed to withstand up to 25,000 mechanical cycles, the XT1S 160 TMD 160-1600 ensures long-lasting performance and reliability.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA (230 V AC) 80 kA (240 V AC) 80 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
112...160 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067446R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.