Short Description: ABB's XT2L 125 TMA 110-550..1100 4p F F UL/CSA is a 4-pole, thermomagnetic circuit breaker with a rated current of 110A and a short circuit rating of 100kA (480V AC). It meets UL/CSA standards for reliable power distribution.
Specifications for XT2L 125 TMA 110-550..1100 4p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 8.8 W
Rated Current (In)
110 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
550â¦1100 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. Reliable Power Distribution
The XT2L 125 TMA 110-550..1100 4p F F UL/CSA ensures consistent and reliable power distribution, making it suitable for a wide range of applications.
2. High-Performance Design
With a thermomagnetic trip unit, this circuit breaker offers high-performance protection against short circuits and overloads, ensuring the safety of your electrical system.
3. UL/CSA Certification
Meets the stringent standards of UL and CSA, providing assurance of compliance with safety regulations and industry standards.
4. Versatile Configuration
Available in a 4-pole configuration, this circuit breaker is versatile and can be used in various electrical systems, including those requiring multiple phases.
5. Durable Construction
Built to last, the XT2L 125 TMA 110-550..1100 4p F F UL/CSA features robust construction and high mechanical durability, ensuring it can withstand the demands of frequent use.
600 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
77...110 A
Short-Circuit Performance Level
L
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 35 kA (250 V DC) 2 Poles in Series 75 kA (500 V DC) 3 Poles in Series 75 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074843R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.