The ABB XT1S 160 TMD 160-1600 4P FF InN=50% circuit breaker is a high-performance, thermomagnetic release device designed for power distribution systems. It features front terminals and a 50% inrush current limiting capability, ensuring reliable and safe operation.
Specifications for XT1S 160 TMD 160-1600 4p F F InN=50%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 15 W
Rated Current (In)
160 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1600 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
Product Highlights
1. Advanced Protection
The XT1S 160 TMD 160-1600 4P FF InN=50% circuit breaker provides robust protection against short circuits and overcurrents, ensuring the safety of your electrical system.
2. High Breaking Capacities
With breaking capacities up to 50 kA at 415 V AC, this circuit breaker can handle high short-circuit currents, making it ideal for demanding applications.
3. Thermomagnetic Release
The thermomagnetic release mechanism ensures reliable operation under various conditions, providing a secure and efficient shutdown in case of an electrical fault.
4. Inrush Current Limiting
The 50% inrush current limiting feature helps to reduce the impact of inrush currents, prolonging the lifespan of your electrical equipment and preventing potential damage.
5. Versatile Connectivity
The circuit breaker supports various fieldbus and IP communication protocols, allowing for seamless integration with data analysis tools on the ABB AbilityTM Cloud platform. This enhances monitoring and control capabilities, making it easier to manage your electrical system.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 80 kA (230 V AC) 80 kA (240 V AC) 80 kA (380 V AC) 50 kA (415 V AC) 37.5 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 17.5 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 35 kA (690 V AC) 8 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
112...160 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067444R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.