The ABB XT2H 160 TMA 125-1250 4p F F InN=50% is a high-performance moulded case circuit breaker designed for reliable power distribution. It features a thermomagnetic release, 4 poles, and a current rating of 125 A, ensuring robust short-circuit breaking capacity and efficient operation.
Specifications for XT2H 160 TMA 125-1250 4p F F InN=50%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.4 W
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
625â¦1250 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
Product Highlights
1. Reliable Power Distribution
The ABB XT2H 160 TMA 125-1250 4p F F InN=50% ensures reliable power distribution with its robust design and high-performance capabilities.
2. Thermomagnetic Release
Equipped with a thermomagnetic release (TMA), this circuit breaker provides efficient and reliable operation under various conditions.
3. High Current Rating
With a current rating of 125 A, this circuit breaker is suitable for applications requiring high current handling.
4. Robust Short-Circuit Breaking Capacity
The XT2H 160 TMA 125-1250 4p F F InN=50% offers robust short-circuit breaking capacity, ensuring the safety and integrity of electrical systems.
5. Compliance with International Standards
This product adheres to IEC standards, ensuring compliance with international safety and performance regulations.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067624R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.