The ABB XT1N 160 TMD 125-1250 4p F F InN=50% is a fixed, four-pole circuit breaker with front terminals and a thermomagnetic release. It is fully rated for neutral and meets IEC standards for rated voltage, current, and short-circuit breaking capacity.
Specifications for XT1N 160 TMD 125-1250 4p F F InN=50%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
Product Highlights
1. Reliable Operation
The XT1N 160 TMD 125-1250 4p F F InN=50% ensures reliable operation in various electrical applications, including transformers, generators, and installations.
2. High Short-Circuit Breaking Capacity
With a rated short-circuit breaking capacity of up to 65 kA at 220-240 V AC, this circuit breaker provides robust protection against electrical faults.
3. Thermomagnetic Release
The thermomagnetic release mechanism ensures quick and efficient tripping in case of an overload or short circuit, providing a high level of safety.
4. Compliance with IEC Standards
The product meets IEC standards for safety and efficiency, ensuring it is suitable for a wide range of applications and regulatory requirements.
5. Durable Design
Constructed with high-quality materials, the XT1N 160 TMD 125-1250 4p F F InN=50% offers excellent mechanical durability, withstanding up to 25,000 operating cycles.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 50 kA (230 V AC) 50 kA (240 V AC) 50 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 18 kA (500 V AC) 15 kA (525 V AC) 11 kA (690 V AC) 5 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 22 kA (690 V AC) 6 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067425R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.