The ABB XT2L 160 Ekip LS/I 10A 3P FF is a fixed three-pole moulded case circuit breaker with front terminals and solid-state release, ideal for AC power distribution applications.
Specifications for XT2L 160 Ekip Dip LS/I In=10A 3p F F
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.1 W
Rated Current (In)
10 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
Product Highlights
1. Reliable Performance
The XT2L 160 Ekip LS/I 10A 3P FF ensures consistent and reliable performance in AC power distribution, making it a trusted choice for various applications.
2. Efficient Operation
With its solid-state release mechanism, this circuit breaker provides efficient operation, minimizing downtime and ensuring smooth power flow.
3. Safety Features
Equipped with front terminals and a robust design, the XT2L 160 Ekip LS/I 10A 3P FF offers enhanced safety features, protecting against electrical shocks and short circuits.
4. Versatile Application
Suitable for a wide range of applications, including industrial and commercial settings, this circuit breaker is versatile and adaptable to various power distribution needs.
5. Compliance and Certifications
The XT2L 160 Ekip LS/I 10A 3P FF meets all relevant IEC standards and EU directives, ensuring compliance with regulatory requirements and providing peace of mind for users.
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
Ekip Dip LS/I
Release Type
EL
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067914R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.