The ABB XT2S 160 TMG 50-200 4p F F is a fixed four-pole circuit breaker with thermomagnetic release, offering reliable protection and high performance in electrical applications.
Product ModelXT2S 160 TMG 50-200 4p F F
Material Number1SDA067754R1
Product ID85718
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. High Short-Circuit Breaking CapacityThe XT2S 160 TMG 50-200 4p F F features a high short-circuit breaking capacity, with ratings up to 85 kA at 220 V AC and 50 kA at 380 V AC, ensuring effective protection against electrical surges.
2
2. Thermomagnetic ReleaseEquipped with a thermomagnetic release mechanism, this circuit breaker provides reliable operation under various temperature conditions, ensuring consistent performance in different environments.
3
3. Front Terminal ConnectionThe front terminal connection type (F) simplifies installation and maintenance, making it easier to connect and disconnect electrical wires without exposing internal components.
4
4. Electrical DurabilityDesigned for high electrical durability, the XT2S 160 TMG 50-200 4p F F can withstand up to 8000 cycles of operation at 120 cycles per hour, ensuring long-lasting performance in demanding applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Generator Protection
5
5. Compliance with IEC StandardsThe circuit breaker complies with IEC standards, ensuring it meets the highest safety and performance requirements for electrical protection in various industries.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 4.09 W
Rated Current (In)
50 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
200 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
(220 V AC) 85 kA (230 V AC) 85 kA (240 V AC) 85 kA (380 V AC) 50 kA (415 V AC) 50 kA (440 V AC) 50 kA (500 V AC) 36 kA (525 V AC) 25 kA (690 V AC) 12 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 3 Poles in Series 50 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMG
Release Type
TM
Setting Range
35...50 A
Short-Circuit Performance Level
S
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067754R1
ABB XT2S 160 TMG 50-200 4p F F - High-Performance Circuit Breaker | INDPRT