The ABB XT2V 160 TMD 12.5-125 4P FF is a high-performance, thermomagnetic release moulded case circuit breaker for reliable power distribution up to 690 V AC and 220 V DC.
Product ModelXT2V 160 TMD 12,5-125 4p F F
Material Number1SDA067702R1
Product ID85640
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliable Operation DescriptionThe ABB XT2V 160 TMD 12.5-125 4P FF is designed with a thermomagnetic release mechanism, ensuring reliable operation under various electrical conditions. Its robust construction guarantees consistent performance over time.
2
2. Efficient Power Distribution DescriptionThis circuit breaker is optimized for efficient power distribution, handling currents up to 125 A with a rated voltage of 690 V AC and 220 V DC. It is ideal for controlling power circuits in industrial and commercial settings.
3
3. Safety Features DescriptionEquipped with advanced safety features, the XT2V 160 TMD 12.5-125 4P FF provides enhanced protection against short circuits and overcurrents. Its thermomagnetic release ensures quick and safe disconnection in case of an emergency.
4
4. Durability and Longevity DescriptionBuilt to last, the XT2V 160 TMD 12.5-125 4P FF is designed to withstand the rigors of continuous operation. Its durable construction and high-quality materials ensure a long service life, reducing the need for frequent replacements.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
5
5. Compliance and Certifications DescriptionThe ABB XT2V 160 TMD 12.5-125 4P FF meets and exceeds international standards for safety and performance. It is certified under EU Directive 2011/65/EU and Amendment 2015/863, ensuring compliance with stringent environmental regulations.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 1.05 W
Rated Current (In)
12.5 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
125 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
(220 V AC) 200 kA (230 V AC) 200 kA (240 V AC) 200 kA (380 V AC) 150 kA (415 V AC) 150 kA (440 V AC) 150 kA (500 V AC) 70 kA (525 V AC) 50 kA (690 V AC) 20 kA (250 V DC) 2 Poles in Series 100 kA (500 V DC) 3 Poles in Series 100 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
8.75...12.5 A
Short-Circuit Performance Level
V
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)