Rated Instantaneous Short-Circuit Current Setting (Ii)
450 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Product Highlights
1. Reliable Operation
The XT1C 160 TMD 16-450 3p F F features a thermomagnetic release, ensuring reliable operation in a wide range of electrical applications.
2. High Durability
Designed to withstand 120 cycles per hour and a total of 8000 cycles, this circuit breaker is built for long-lasting performance in demanding environments.
3. Compliance and Certifications
Meets IEC standards and includes CE certification, ensuring compliance with international safety regulations.
4. Efficient Design
With a compact size and front terminals, the XT1C 160 TMD 16-450 3p F F is designed for easy installation and minimal space requirements.
5. Versatile Application
Suitable for use in both AC and DC systems, this circuit breaker can be applied in a variety of electrical installations, including transformers and generators.
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Release
TMD
Release Type
TM
Setting Range
11.2...16 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA080825R1