Short Description: The ABB XT2L 160 TMA 160-1600 3P FF is a high-performance, three-pole circuit breaker with a thermomagnetic release, designed for applications requiring up to 1600 A short-circuit breaking capacity and 160 A rated current[1][3].
Rated Instantaneous Short-Circuit Current Setting (Ii)
80â¦1600 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
Product Highlights
Product Feature
1. High Short-Circuit Breaking Capacity The XT2L 160 TMA 160-1600 3P FF boasts a short-circuit breaking capacity of up to 1600 A, ensuring reliable operation even in high-stress electrical environments.
Product Feature
2. Thermomagnetic Release Equipped with a thermomagnetic release, this circuit breaker provides a robust mechanism for interrupting electrical currents, ensuring safety and reliability.
Product Feature
3. Durable Design Constructed with high-quality materials, the XT2L 160 TMA 160-1600 3P FF is designed to withstand frequent operations, with a mechanical durability of up to 25,000 cycles.
Product Feature
4. Front Terminal Connection Featuring front terminals, this circuit breaker offers easy and convenient connection points, simplifying installation and maintenance processes.
Product Feature
5. Compliance with International Standards The XT2L 160 TMA 160-1600 3P FF meets IEC standards and is CE compliant, ensuring it meets the highest safety and performance standards for electrical applications.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
11.2...16 A
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067648R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.