ABB's XT1H 125 TMF 125-1250 4P FF UL/CSA circuit breaker is designed for reliable and safe power distribution. It features thermal-magnetic fixed trip units and is certified for 480V applications, ensuring compliance with UL/CSA standards.
Specifications for XT1H 125 TMF 125-1250 4p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250 A
Rated Operational Voltage
600Y/347 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. Reliable Power Distribution
The XT1H 125 TMF 125-1250 4P FF UL/CSA circuit breaker ensures consistent and reliable power distribution, making it ideal for various industrial applications.
2. Thermal-Magnetic Fixed Trip Units
Equipped with thermal-magnetic fixed trip units, this circuit breaker provides robust protection against overcurrent conditions, ensuring the safety of your electrical system.
3. UL/CSA Certification
Certified by UL and CSA, this product meets the highest standards for safety and performance in electrical distribution systems.
4. Versatile Application
Suitable for a wide range of distribution levels from main low voltage switchboards to subswitchboards, making it a versatile solution for various electrical installations.
5. High Specific Let-Through Current
The circuit breaker features high specific let-through current, which helps in reducing the impact of short circuits and ensuring minimal damage to the electrical system.
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
125 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 100 kA (480 V AC) 65 kA (600Y / 347 V AC) 25 kA (250 V DC) 2 Poles in Series 50 kA (500 V DC) 4 Poles in Series Kind 50 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074723R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.