The ABB XT2H 125 TMA 100-500..1000 3p F F UL/CSA is a reliable, three-pole molded case circuit breaker ideal for power distribution applications. It offers thermomagnetic release and front terminal connections, ensuring efficient and safe operation.
Specifications for XT2H 125 TMA 100-500..1000 3p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 8.1 W
Rated Current (In)
100 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500â¦1000 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. High-Performance Design
The ABB XT2H 125 TMA 100-500..1000 3p F F UL/CSA is engineered to handle high currents, making it suitable for demanding power distribution applications.
2. Thermomagnetic Release
Equipped with a thermomagnetic release mechanism, this circuit breaker provides reliable and efficient operation under various conditions.
3. Front Terminal Connections
Featuring front terminals, the XT2H 125 TMA ensures easy and secure connections, reducing installation time and improving overall efficiency.
4. UL/CSA Certification
Meets UL/CSA standards, ensuring compliance with safety regulations and providing peace of mind for users.
5. Durable Construction
Built with durable materials, this circuit breaker can withstand high mechanical durability, with up to 25,000 cycles, and electrical durability of up to 8,000 cycles.
600 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
70...100 A
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA (480 V AC) 65 kA (600 V AC) 25 kA (250 V DC) 2 Poles in Series 65 kA (500 V DC) 3 Poles in Series 65 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074800R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.