Short Description: ABB XT2H 125 MCP In=70 3P FF UL/CSA - Reliable, three-pole circuit breaker with magnetic release and front terminals, meeting UL and CSA standards for motor protection and energy management.
Specifications for XT2H 125 MCP In=70 3p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 5.5 W
Rated Current (In)
70 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
210â¦770 A
Rated Operational Voltage
600 V AC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
Product Feature
1. Reliability and Safety The ABB XT2H 125 MCP In=70 3P FF UL/CSA is designed to provide reliable and safe operation, ensuring the protection of your electrical system and equipment. Its magnetic release mechanism ensures quick and efficient operation in case of an overload.
Product Feature
2. Compliance with Standards This circuit breaker meets the stringent standards set by UL and CSA, ensuring it is suitable for a wide range of applications. Its compliance with these standards guarantees that it will perform consistently and reliably in various environments.
Product Feature
3. Efficient Motor Protection The XT2H 125 MCP In=70 3P FF UL/CSA is specifically designed for motor protection, providing robust and efficient operation to safeguard your motors from overloads and short circuits. Its high interrupting capacity ensures that it can handle heavy currents without failing.
Product Feature
4. Front Terminal Connection The front terminal connection of the XT2H 125 MCP In=70 3P FF UL/CSA makes it easy to install and maintain. The bolt-type terminals ensure secure connections, reducing the risk of electrical faults and improving overall system reliability.
Product Feature
5. Environmental Considerations ABB’s commitment to sustainability is evident in the design of the XT2H 125 MCP In=70 3P FF UL/CSA. It adheres to circular design principles, aiming to reduce waste and increase recyclability. This aligns with the growing demand for eco-friendly products in the electrical industry.
600 V
Recommended Screw Driver
Main Circuit M6
Release
MA
Release Type
M
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA (480 V AC) 65 kA (600 V AC) 25 kA (250 V DC) 2 Poles in Series 65 kA (500 V DC) 3 Poles in Series 65 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074887R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.