The ABB XT1C 160 TMD 100-1000 3p FF is a versatile, adjustable 3-pole circuit breaker designed for industrial and commercial use. It features thermal-magnetic protection with adjustable settings from 100 to 1000A, ensuring reliable performance and ease of installation.
Rated Instantaneous Short-Circuit Current Setting (Ii)
1000 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
Product Highlights
1. Adjustable Thermal-Magnetic Trip
The XT1C 160 TMD offers adjustable thermal-magnetic trip settings from 100 to 1000A, allowing for precise customization to meet various application requirements.
2. High Short-Circuit Breaking Capacity
With a high short-circuit breaking capacity, this circuit breaker provides robust protection against electrical surges, ensuring the safety of your electrical system.
3. Reliable Performance
Designed with thermal-magnetic protection, the XT1C 160 TMD ensures reliable performance under various operating conditions, making it a trusted choice for industrial and commercial applications.
4. Easy Installation
The fixed-front terminal connection simplifies installation, reducing setup time and ensuring a secure connection that meets your needs.
5. Versatile Application
Suitable for a wide range of applications, from industrial machinery to commercial power distribution systems, the XT1C 160 TMD offers flexibility and reliability in one package.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
70...100 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067397R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.