Short Description: ABB XT2L 125 TMA 80-400..800 3P FF UL/CSA: High-performance, three-pole moulded case circuit breaker with thermomagnetic release, UL/CSA certified for reliable power distribution.
Specifications for XT2L 125 TMA 80-400..800 3p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 5.8 W
Rated Current (In)
80 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
400â¦800 A
Rated Operational Voltage
600 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. Reliable Power Distribution
The ABB XT2L 125 TMA 80-400..800 3P FF UL/CSA ensures reliable power distribution with its robust design and high interrupting capacity, making it ideal for various industrial applications.
2. UL/CSA Certified
This circuit breaker meets the stringent safety standards of UL (Underwriters Laboratories) and CSA (Canadian Standards Association), ensuring it is safe for use in a wide range of environments.
3. Thermomagnetic Release
The thermomagnetic release mechanism provides fast and efficient tripping in case of overcurrent conditions, ensuring the circuit breaker operates reliably under various load conditions.
4. High Interrupting Capacity
With an interrupting rating of up to 35 kA at 600 V AC, this circuit breaker can handle high short-circuit currents, making it suitable for demanding industrial applications.
5. Eco-Friendly Design
ABB's commitment to sustainability is reflected in the XT2L's design for closing resource loops, with a recyclability rate of 58.1% and compliance with RoHS and REACH regulations, ensuring a more environmentally friendly solution.
600 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
56...80 A
Short-Circuit Performance Level
L
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 200 kA (480 V AC) 100 kA (600 V AC) 35 kA (250 V DC) 2 Poles in Series 75 kA (500 V DC) 3 Poles in Series 75 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074826R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.