ABB XT1C 160 TMD 80-800 3p F F: High-performance moulded case circuit breaker with TMD release, IEC compliant, and suitable for power distribution applications.
Rated Instantaneous Short-Circuit Current Setting (Ii)
800 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
Product Highlights
1. High Reliability and Safety
The XT1C 160 TMD 80-800 3p F F is designed to meet IEC standards, ensuring high reliability and safety in power distribution applications. Its thermomagnetic release (TMD) provides reliable tripping performance under various conditions.
2. Versatile Application
This circuit breaker is suitable for a wide range of applications, including power distribution, transformer, and generator installations. Its versatility makes it an ideal choice for various electrical systems.
3. Efficient Performance
With a rated current of 80 A and a rated voltage of 690 V, the XT1C 160 TMD 80-800 3p F F offers efficient performance in handling electrical loads. Its power loss at rated operating conditions per pole is 4.8 W, ensuring minimal energy consumption.
4. Durable Construction
The circuit breaker is built to withstand mechanical durability, with a number of operations up to 25,000 cycles. It also supports electrical durability with up to 8,000 cycles per hour, making it a durable choice for long-term use.
5. Compliance with Regulations
The XT1C 160 TMD 80-800 3p F F complies with EU Directive 2011/65/EU and Amendment 2015/863, ensuring RoHS compliance. Additionally, it meets various certifications including IEC and CE, making it a compliant choice for regulatory requirements.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
56...80 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067396R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.