The ABB XT1S 125 TMF 40-500 4P F F UL/CSA is a high-performance, UL/CSA certified molded case circuit breaker designed for industrial applications. It ensures reliable and safe electrical distribution.
Specifications for XT1S 125 TMF 40-500 4p F F UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 2.6 W
Rated Current (In)
40 A
Rated Instantaneous Short-Circuit Current Setting (Ii)
500 A
Rated Operational Voltage
600Y/347 V AC 500 V DC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
Product Highlights
1. High Performance and Efficiency
The ABB XT1S 125 TMF 40-500 4P F F UL/CSA is engineered to provide efficient electrical distribution, ensuring optimal performance in various industrial settings.
2. UL and CSA Certification
This product meets the stringent standards of UL and CSA, guaranteeing its reliability and safety in electrical applications.
3. Versatile Industrial Use
Designed for a wide range of industrial applications, this circuit breaker is versatile and can be used in various environments.
4. Reliable Electrical Distribution
With its robust design, the XT1S 125 TMF 40-500 4P F F UL/CSA ensures reliable electrical distribution, minimizing downtime and ensuring continuous operation.
5. Compact Dimensions
The compact dimensions of the XT1S 125 TMF 40-500 4P F F UL/CSA make it easy to integrate into existing electrical systems, saving space and enhancing overall efficiency.
600Y/347 V
Recommended Screw Driver
Main Circuit M6
Release
TMF
Release Type
TM
Setting Range
40 A
Short-Circuit Performance Level
S
Standards
UL489
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 65 kA (480 V AC) 35 kA (600Y / 347 V AC) 22 kA (250 V DC) 2 Poles in Series 42 kA (500 V DC) 4 Poles in Series Kind 50 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4927 >> Molded case circuit breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA074684R1