ABB AF265-30-22-33: 3-pole, 100-250 VAC/VDC, 400A, 250 HP. Ideal for motor starting, isolation, and distribution applications. Reliable and efficient control for industrial use.
Product ModelAF265-30-22-33
Material Number1SFL547002R3322
Product ID84606
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Versatile ApplicationThe ABB AF265-30-22-33 contactor is designed for a variety of applications including motor starting, isolation, and distribution, making it a versatile solution for industrial control systems.
2
2. Wide Voltage RangeOperates within a wide voltage range of 100-250 VAC/VDC, ensuring compatibility with different electrical systems and reducing the need for multiple contactors.
3
3. High Power HandlingSupports up to 400 amps and 250 HP, making it suitable for high-power applications such as large motors and heavy machinery.
4
4. Reliable PerformanceBuilt with high-quality components, the AF265-30-22-33 contactor provides reliable performance and long-lasting operation, minimizing downtime and maintenance costs.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
140 mm
Product Net Depth / Length
195.5 mm
Product Net Height
225 mm
Product Net Weight
3.9 kg
Number of Main Contacts NO
3
Number of Main Contacts NC
0
5
5. Efficient ControlDesigned for efficient control, this contactor reduces energy consumption and minimizes panel energy consumption, contributing to overall system efficiency and cost savings.
Number of Auxiliary Contacts NO
2
Number of Auxiliary Contacts NC
2
Rated Operational Voltage
Main Circuit 1000 V
Rated Frequency (f)
Main Circuit 60 Hz
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Π= 40 °C 400 A
Rated Operational Current AC-1 (Ie)
(1000 V) 40 °C 350 A (1000 V) 60 °C 300 A (1000 V) 70 °C 240 A (690 V) 40 °C 400 A (690 V) 70 °C 290 A
Rated Operational Current AC-3 (Ie)
(415 V) 55 °C 265 A (440 V) 55 °C 265 A (500 V) 55 °C 250 A (690 V) 55 °C 250 A (1000 V) 55 °C 113 A (380 / 400 V) 55 °C 265 A (220 / 230 / 240 V) 55 °C 265 A
Rated Short-time Withstand Current Low Voltage (Icw)
at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 2120 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 865 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2650 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1224 A
Maximum Electrical Switching Frequency
(AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour
Rated Insulation Voltage (Ui)
acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
8 kV
Mechanical Durability
5 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) Uc (at θ ⤠70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 17.5 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 17.5 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 385 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 385 V·A Pull-in at Max. Rated Control Circuit Voltage DC 410 W
Operate Time
Between Coil De-energization and NO Contact Opening 37 ... 47 ms Between Coil Energization and NO Contact Closing 25 ... 55 ms
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
Terminal Type
Main Circuit: Bars
NEMA Size
5
Continuous Current Rating NEMA
270 A
Horsepower Rating NEMA
(200 V AC) Three Phase 75 Hp (230 V AC) Three Phase 100 Hp (460 V AC) Three Phase 200 Hp (575 V AC) Three Phase 200 Hp
Maximum Operating Voltage UL/CSA
Main Circuit 1000 V
Horsepower Rating UL/CSA
(200 ... 208 V AC) Three Phase 40 Hp (200 V AC) Three Phase 75 hp (208 V AC) Three Phase 75 hp (220 ... 240 V AC) Three Phase 40 Hp (220 ... 240 V AC) Three Phase 100 hp (440 ... 480 V AC) Three Phase 100 Hp (440 ... 480 V AC) Three Phase 200 hp (550 ... 600 V AC) Three Phase 125 Hp (550 ... 600 V AC) Three Phase 250 hp
Ambient Air Temperature
Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 55 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °C Close to Contactor for Storage -40 ... 70 °C