The ABB Tmax XT2L 160 TMD 6.3-63 4P FF is a fixed four-pole moulded case circuit breaker with thermomagnetic release and front terminals, ideal for transformer, generator, and installation protection applications.
Rated Instantaneous Short-Circuit Current Setting (Ii)
63 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
Product Highlights
1. Reliable Performance
The ABB Tmax XT2L 160 TMD 6.3-63 4P FF is designed to provide reliable performance under various operating conditions, ensuring consistent protection for your electrical systems.
2. Thermomagnetic Release
Equipped with a thermomagnetic release, this circuit breaker automatically trips in case of an overload or short circuit, ensuring safety and preventing damage to your equipment.
3. Front Terminal Connection
The front terminal connection makes installation and maintenance easier, reducing the time and effort required for setup and repairs.
4. IEC Standards Compliance
The XT2L 160 TMD meets IEC standards for short-circuit breaking capacity, ensuring that it can handle high current surges effectively and safely.
5. Durable Design
Constructed with durable materials, this circuit breaker is designed to withstand the rigors of frequent operations and harsh environmental conditions, providing long-lasting service.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
4.41...6.3 A
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067655R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?