Short Description: The ABB XT2L 160 TMA 160-1600 4p FF InN=50% is a fixed, four-pole circuit breaker with front terminals and thermomagnetic release, rated for 800-1600 A. It ensures reliable operation and high short-circuit breaking capacity, making it ideal for various electrical installations.
Specifications for XT2L 160 TMA 160-1600 4p F F InN=50%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
120 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.45 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1002
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 16.15 W
Rated Current (In)
160 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
800â¦1600 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
Product Highlights
1. High Short-Circuit Breaking Capacity
The XT2L 160 TMA 160-1600 4p FF InN=50% boasts an impressive short-circuit breaking capacity, with ratings up to 150 kA at 220-240 V AC and 120 kA at 380-440 V AC.
2. Reliable Thermomagnetic Release
Equipped with a thermomagnetic release, this circuit breaker ensures reliable operation under various conditions, providing a safe and efficient shutdown in case of an overload or short circuit.
3. Versatile Application
Designed for a wide range of electrical applications, including transformers, generators, and installations, the XT2L 160 TMA 160-1600 4p FF InN=50% is a versatile solution for maintaining electrical safety and efficiency.
4. Compliance with Safety Standards
The product meets stringent safety standards, including compliance with EU Directive 2011/65/EU and Amendment 2015/863, ensuring it adheres to the latest environmental regulations.
5. Durable Construction
Built with durable materials, the XT2L 160 TMA 160-1600 4p FF InN=50% offers long-lasting performance and mechanical durability, withstanding up to 25,000 operational cycles.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMA
Release Type
TM
Setting Range
112...160 A
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067669R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.