The ABB NFZ62EK-23 is a 250 VDC contactor relay designed for high-reliability applications. It features built-in surge protection and push-in spring terminals for easy installation.
Product ModelNFZ62EK-23
Material Number1SBH136005R2362
Product ID84353
Stock on Request
Last updated: 8/29/2026
Key Features
1
1. Reliability and EfficiencyThe ABB NFZ62EK-23 is engineered to provide consistent and efficient operation, ensuring your system runs smoothly without interruptions.
2
2. Built-in Surge ProtectionEquipped with advanced surge protection, this contactor relay safeguards your equipment from voltage spikes and electrical surges, extending its lifespan.
3
3. Easy InstallationFeaturing push-in spring terminals, the NFZ62EK-23 simplifies the installation process, reducing setup time and minimizing the risk of errors.
4
4. Durable DesignConstructed with high-quality materials, this contactor relay is designed to withstand harsh environments and heavy usage, making it a reliable choice for demanding applications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Product Net Width
45 mm
Product Net Depth / Length
110.5 mm
Product Net Height
92.3 mm
Product Net Weight
0.36 kg
Number of Auxiliary Contacts NO
6
Number of Auxiliary Contacts NC
2
5
5. Versatile CompatibilityCompatible with both 50 and 60 Hz frequencies, the ABB NFZ62EK-23 can be used in a wide range of applications, from industrial automation to commercial settings.
Standards
IEC/EN 60947-1, IEC/EN 60947-5-1, UL 508, CSA C22.2 No. 14-13
(500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (400 / 440 V) 3 A
Rated Short-time Withstand Current Low Voltage (Icw)
for 0.1 s 140 A for 1 s 100 A
Maximum Electrical Switching Frequency
(AC-15) 1200 cycles per hour (DC-13) 900 cycles per hour
Rated Operational Current DC-13 (Ie)
(24 V) 6 A / 144 W (48 V) 2.8 A / 134 W (72 V) 1 A / 72 W (110 V) 0.55 A / 60 W (125 V) 0.55 A / 69 W (220 V) 0.27 A / 60 W (250 V) 0.27 A / 68 W (400 V) 0.15 A / 60 W (500 V) 0.13 A / 65 W (600 V) 0.1 A / 60 W
Rated Insulation Voltage (Ui)
acc. to IEC 60947-5-1 690 V acc. to UL/CSA 600 V
Rated Impulse Withstand Voltage (Uimp)
6 kV
Maximum Mechanical Switching Frequency
6000 cycles per hour
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V 60 Hz 100 ... 250 V DC Operation 100 ... 250 V
Operate Time
Between Coil De-energization and NC Contact Closing 13 ... 98 ms Between Coil De-energization and NO Contact Opening 11 ... 95 ms Between Coil Energization and NC Contact Opening 38 ... 90 ms Between Coil Energization and NO Contact Closing 40 ... 95 ms
Mounting on DIN Rail
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Terminal Type
Push-in Spring Terminals
Connecting Capacity Auxiliary Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG
Connecting Capacity Control Circuit UL/CSA
Rigid Solid 1/2x 18-14 AWG
Ambient Air Temperature
Close to Contactor for Storage -60 ... +80 °C Near Contactor for Operation in Free Air -40 ... 70 °C Near Contactor for Operation in Free Air (0.85 ... 1.1 Uc) -40 ... +60 °C Near Contactor for Operation in Free Air (Uc) -40 ... 70 °C
Climatic Withstand
Category B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Vibrations
4g Closed Position & 2g Open position 5 ... 300 Hz