The ABB XT1C 160 TMD 125-1250 4p F F InN=50% is a fixed four-pole circuit breaker with thermomagnetic release and front terminals. It offers reliable performance, high durability, and efficient power distribution.
Specifications for XT1C 160 TMD 125-1250 4p F F InN=50%
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
101.6 mm
Product Net Height
130 mm
Product Net Depth / Length
70 mm
Product Net Weight
1.4 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0080
Connecting Capacity Main Circuit
Busbar 45.5 ... 80 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 10.7 W
Rated Current (In)
125 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1250 A
Rated Insulation Voltage (Ui)
800 V
Rated Operational Voltage
Product Highlights
1. Reliable Performance
The ABB XT1C 160 TMD 125-1250 4p F F InN=50% is designed to provide consistent and reliable performance in a wide range of electrical applications, ensuring that your system operates smoothly and efficiently.
2. High Durability
With a mechanical durability of 25,000 cycles and electrical durability of 25,000 operations, this circuit breaker is built to withstand the demands of heavy use, extending its lifespan and reducing maintenance needs.
3. Efficient Power Distribution
Equipped with thermomagnetic release, this circuit breaker ensures efficient power distribution by quickly and accurately interrupting electrical currents in case of a short circuit, minimizing damage to your equipment.
4. Front Terminal Connection
The front terminal connection makes installation and maintenance easier, allowing for quick and secure connections without the need for complex wiring or additional tools.
5. Compliance with EU Directives
The XT1C 160 TMD 125-1250 4p F F InN=50% complies with EU Directive 2011/65/EU and Amendment 2015/863, ensuring that it meets the highest standards of environmental sustainability and safety, making it a responsible choice for your electrical needs.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 12.5 kA (500 V AC) 9 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
(220 V AC) 40 kA (230 V AC) 40 kA (240 V AC) 40 kA (380 V AC) 25 kA (415 V AC) 25 kA (440 V AC) 25 kA (500 V AC) 18 kA (525 V AC) 8 kA (690 V AC) 4 kA (250 V DC) 2 Poles in Series 25 kA (500 V DC) 3 Poles in Series 25 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
87.5...125 A
Short-Circuit Performance Level
C
Standards
IEC60947-2
Sub-type
XT1
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067407R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.