The ABB XT2L 160 MA 100 Im=600...1400 3p F F is a fixed three-pole circuit breaker with front terminals and magnetic release, rated for 100 A at 690 V AC, with a short-circuit current rating of 600 to 1400 A.
Specifications for XT2L 160 MA 100 Im=600...1400 3p F F
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.1 kg
Circuit Breaker Type to be Associated
Motor Protection
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 8.08 W
Rated Current (In)
100 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
600â¦1400 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
Product Highlights
1. High-Performance Design
The XT2L 160 MA 100 Im=600...1400 3p F F features a robust design that ensures reliable operation under demanding electrical conditions, making it suitable for a wide range of applications.
2. Magnetic Release
Equipped with a magnetic release mechanism, this circuit breaker provides quick and efficient disconnection in case of an electrical fault, ensuring safety and minimizing downtime.
3. Three-Pole Configuration
Designed as a three-pole circuit breaker, it can handle three-phase electrical systems, providing comprehensive protection for your electrical infrastructure.
4. Wide Short-Circuit Current Rating
With a short-circuit current rating of 600 to 1400 A, this circuit breaker is capable of handling high levels of electrical stress, ensuring it can interrupt short circuits effectively.
5. Compliance with IEC Standards
The XT2L 160 MA 100 Im=600...1400 3p F F meets IEC standards, ensuring that it adheres to the highest safety and performance requirements, making it a reliable choice for your electrical needs.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
(220 V AC) 150 kA (230 V AC) 150 kA (240 V AC) 150 kA (380 V AC) 120 kA (415 V AC) 120 kA (440 V AC) 100 kA (500 V AC) 60 kA (525 V AC) 36 kA (690 V AC) 18 kA (250 V DC) 2 Poles in Series 85 kA (500 V DC) 3 Poles in Series 85 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
MA
Release Type
M
Short-Circuit Performance Level
L
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067789R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.
Need Help Checking This Part?
Ask about specifications, condition or a suitable alternative.