ABB XT4N 250 TMA 200-2000 4P FF UL/CSA: A reliable, thermomagnetic release circuit breaker for 4-pole applications, meeting UL/CSA standards for safety and performance.
Product ModelXT4N 250 TMA 200-2000 4p F F InN=50%
Material Number1SDA068104R1
Product ID83694
Stock on Request
Last updated: 8/29/2026
Key Features
1
Feature1. Reliable Energy Management The ABB XT4N 250 TMA 200-2000 4P FF UL/CSA circuit breaker is designed to provide reliable energy management in various industrial settings. Its robust construction ensures consistent performance under heavy loads.
2
Feature2. Thermomagnetic Release Equipped with a thermomagnetic release mechanism, this circuit breaker offers fast and efficient tripping in case of short circuits or overloads, ensuring the safety of your electrical system.
3
Feature3. UL/CSA Compliance Meets the stringent standards set by UL and CSA, ensuring that the circuit breaker adheres to the highest safety and performance criteria. This compliance makes it suitable for a wide range of applications.
4
Feature4. Four-Pole Configuration Designed for four-pole applications, this circuit breaker provides comprehensive protection for your electrical system. It can handle high currents and is ideal for use in heavy-duty industrial settings.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Specifications may be subject to change without notice
Parameter
Value
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
140 mm
Product Net Height
160 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
2.9 kg
Circuit Breaker Type to be Associated
Power Distribution
5
Feature5. Front Terminal Connection The front terminal connection type allows for easy installation and maintenance. The bolt terminal type ensures secure connections, reducing the risk of electrical faults and improving overall system reliability.
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Version
F
CAD Dimensional Drawing
1SDH001295R0677
Connecting Capacity Main Circuit
Busbar 85..200 mm²
Current Type
AC/DC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
4P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 11.88 W
Rated Current (In)
200 A
Rated Frequency (f)
50 / 60 Hz
Rated Impulse Withstand Voltage (Uimp)
8 kV
Rated Instantaneous Short-Circuit Current Setting (Ii)
1000â¦2000 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
690 V AC 750 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
(220 V AC) 65 kA (230 V AC) 65 kA (240 V AC) 65 kA (380 V AC) 36 kA (415 V AC) 36 kA (440 V AC) 36 kA (500 V AC) 30 kA (525 V AC) 20 kA (690 V AC) 10 kA (250 V DC) 2 Poles in Series 36 kA (500 V DC) 2 Poles in Series 36 kA (500 V DC) 3 Poles in Series 36 kA
Rated Uninterrupted Current (Iu)
250 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M8
Release
TMA
Release Type
TM
Setting Range
140...200 A
Short-Circuit Performance Level
N
Standards
IEC60947-2
Sub-type
XT4
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
8 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)