The ABB XT2H 160 TMD 1,6-16 3p F F is a high-performance, three-pole circuit breaker with thermomagnetic release, designed for reliable operation in various electrical systems.
Rated Instantaneous Short-Circuit Current Setting (Ii)
16 A
Rated Insulation Voltage (Ui)
1000 V
Rated Operational Voltage
Product Highlights
1. High Reliability and Safety
The XT2H 160 TMD 1,6-16 3p F F is engineered with a thermomagnetic release mechanism, ensuring reliable and safe operation under various electrical conditions.
2. Versatile Voltage Compatibility
Compatible with both 690V AC and 500V DC, making it suitable for a wide range of applications including industrial and commercial settings.
3. High Current Rating
With a rated uninterrupted current of 160A, this circuit breaker is designed to handle high electrical loads, providing continuous operation without interruption.
4. Durable Design
Built to withstand 120 cycles per hour and 8000 cycles in total, ensuring long-lasting performance and minimal maintenance needs.
5. Compliance with International Standards
Meets IEC standards, ensuring compliance with international safety and performance regulations, providing peace of mind for users worldwide.
690 V AC 500 V DC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA
(220 V AC) 100 kA (230 V AC) 100 kA (240 V AC) 100 kA (380 V AC) 70 kA (415 V AC) 70 kA (440 V AC) 65 kA (500 V AC) 50 kA (525 V AC) 30 kA (690 V AC) 15 kA (250 V DC) 2 Poles in Series 70 kA (500 V DC) 3 Poles in Series 70 kA
Rated Uninterrupted Current (Iu)
160 A
Rated Voltage (Ur)
690 V
Recommended Screw Driver
Main Circuit M6
Release
TMD
Release Type
TM
Setting Range
1.12...1.6 A
Short-Circuit Performance Level
H
Standards
IEC60947-2
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
UNSPSC
39120000
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA067584R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.