The ABB XT2H 125 Ekip M Dip I In=10A 3P FF MCP-UL/CSA is a versatile, UL/CSA certified molded case circuit breaker designed for various distribution levels. It offers a solid-state release and front terminal connection, making it an excellent choice for ensuring reliable and efficient operation in electrical installations.
Specifications for XT2H 125 Ekip M Dip I In=10A 3p F F MCP-UL/CSA
Parameter
Value
Environmental Information
9AKK108467A6707
Product Net Width
90 mm
Product Net Height
130 mm
Product Net Depth / Length
82.5 mm
Product Net Weight
1.12 kg
Circuit Breaker Type to be Associated
Power Distribution
Product Main Type
SACE Tmax XT
Product Name
Moulded Case Circuit Breaker
Product Type
Automatic Circuit Breaker
Suitable for Product Class
SACE Tmax XT
Version
F
CAD Dimensional Drawing
1SDH002230A1001
Connecting Capacity Main Circuit
Busbar 32.5..100 mm²
Current Type
AC
Electrical Durability
120 cycles per hour 8000 cycle
Mechanical Durability
240 cycles per hour 25000 cycle
Number of Poles
3P
Opening Time
CB with SOR 15 ms CB with UVR 15 ms
Order Multiple
1 piece
Power Loss
at Rated Operating Conditions per Pole 0.1 W
Rated Current (In)
10 A
Rated Operational Voltage
600 V AC
Rated Uninterrupted Current (Iu)
125 A
Rated Voltage (Ur)
600 V
Recommended Screw Driver
Main Circuit M6
Product Highlights
1. Reliable Performance
The ABB XT2H 125 Ekip M Dip I In=10A 3P FF MCP-UL/CSA is engineered to provide reliable performance under various electrical conditions, ensuring consistent operation and minimizing downtime.
2. UL/CSA Certification
This circuit breaker is certified by UL and CSA, meeting the highest standards for safety and performance in North America. This certification ensures that the product meets rigorous testing criteria, providing peace of mind for users.
3. Solid-State Release
The solid-state release mechanism in the XT2H 125 Ekip M Dip I In=10A 3P FF MCP-UL/CSA offers fast and precise tripping, reducing the risk of electrical shocks and ensuring quick response to overcurrent conditions.
4. Front Terminal Connection
The front terminal connection makes installation and maintenance easier, allowing for quick access to the circuit breaker's internal components. This design enhances user convenience and reduces the time required for repairs.
5. Versatile Application
The ABB XT2H 125 Ekip M Dip I In=10A 3P FF MCP-UL/CSA is suitable for a wide range of applications, from main low voltage switchboards to subswitchboards. Its versatility makes it an ideal choice for various electrical distribution systems, ensuring it can meet the needs of diverse projects.
Release
Ekip M Dip I
Release Type
EL
Short-Circuit Performance Level
H
Standards
UL489
Sub-type
XT2
Terminal Connection Type
Front
Terminal Type
Bolt
Tightening Torque
6 N·m
Interrupting Rating acc. to UL489
(240 V AC) 150 kA (480 V AC) 65 kA (600 V AC) 25 kA
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4932 >> 3 Pole Non-Interchangeable Trip Electronic Circuit Breakers
Object Classification Code
Q
UNSPSC
39121616
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Manufacturer ID
1SDA075070R1
Specifications may change. Confirm the exact model, revision and offered condition with your quotation.